Fan selection ranges and performance charts, SCR scrubbing tower specifications and adsorbent performance data, all from the Winfan catalogues. Selection data is for guidance only — every final selection is confirmed by our engineers.
Catalogue selection ranges for the FRP TF/HF series and the metal TDC/TAA series, from the Winfan fan catalogues (FRP Fan Series, November 2023; Metal Fan Series, April 2023). All figures are approximate (≈), read from the catalogue performance charts. Selection data for guidance only — final selection confirmed by our engineers.
| Model | Airflow (≈ m³/h) | Static pressure (≈ Pa) |
|---|---|---|
| TF-121B | ≈600–2,100 | ≈100–1,600 |
| TF-151B | ≈700–5,500 | ≈300–2,100 |
| TF-181B | ≈3,000–10,000 | ≈300–2,700 |
| TF-211B | ≈3,200–12,500 | ≈300–2,700 |
| TF-241B | ≈4,000–18,100 | ≈300–2,700 |
| TF-271B | ≈8,500–23,500 | ≈300–2,700 |
| TF-301B | ≈11,500–28,500 | ≈900–2,700 |
| TF-331B | ≈12,000–36,000 | ≈900–2,700 |
| TF-361B | ≈18,000–46,000 | ≈900–2,700 |
| TF-421B | ≈30,000–60,000 | ≈900–2,700 |
| TF-481B | ≈44,000–80,000 | ≈900–2,700 |
| TF-541B | ≈60,000–108,000 | ≈900–2,700 |
| TF-601B | ≈70,000–127,000 | ≈900–2,700 |
| TF-721B | ≈84,000–150,000 | ≈1,200–2,700 |
Series envelope: airflow ≈600–150,000 m³/h, static pressure ≈100–2,700 Pa. Power (kW) ratings include drive losses; performance ratings do not include system effects of fan accessories (catalogue note). Selection data for guidance only — final selection confirmed by our engineers.
Catalogue design features of the FRP series: backward-inclined impeller with logarithmic-profile, high-strength formed blades; oil-cooled bearing housing for long bearing life, easy maintenance and low mechanical noise; casing and steel-frame fasteners integrally pre-embedded during moulding, so corrosion cannot destroy the fixings; 24-hour, year-round service support.
| Sizes | Airflow (≈ m³/h) | Static pressure (≈ Pa) |
|---|---|---|
| HF-121B – HF-721B (11 sizes) | ≈50–100,000 | ≈400–5,900 |
For high-resistance corrosive-gas duty: wastewater deodorization, sludge drying, pharmaceutical chemicals, fibreglass production, rare-earth extraction, paper-mill anaerobic systems and acid recovery. Selection data for guidance only — final selection confirmed by our engineers.
| Sizes | Airflow (≈ m³/h) | Static pressure (≈ Pa) |
|---|---|---|
| TDC-4.5 – TDC-18 (12 sizes) | ≈1,400–130,000 | ≈1,000–5,200 |
Selection data for guidance only — final selection confirmed by our engineers.
| Sizes | Airflow (≈ m³/h) | Static pressure (≈ Pa) |
|---|---|---|
| TAA-3.2 – TAA-20 (17 sizes) | ≈600–256,000 | ≈450–4,200 |
Selection data for guidance only — final selection confirmed by our engineers.
B TF-241 B
Examples: TF-151B — medium/low-pressure fan, size 151, belt drive. HF-181C — high-pressure fan, size 181, coupling drive.
TDC-8 C
Full per-size performance curves and dimension tables for all eight outlet directions are available in the catalogue — ask our engineers for the pages for your selected size.
The maximum pressure of up to 12,000 Pa quoted on this page refers to Dingyu's custom ultra-high-pressure FRP fans — a separate, made-to-order line for ultra-high-resistance tail-gas systems. It is not part of the standard HF catalogue series above, whose selection envelope tops out at ≈5,900 Pa. If your system resistance is in that range, talk to our engineers about a custom selection.
| Model | Tower dia. A (mm) | Tower height B (mm) | Gas inlet C (mm) | Packing depth D (mm) | Demister depth F (mm) | Circulation water (L/min) | Airflow (m³/h) |
|---|---|---|---|---|---|---|---|
| SCR-600 | 600 | 4,300 | 300 | 1,200 | 600 | 70 | 2,000 |
| SCR-800 | 800 | 4,400 | 400 | 1,200 | 600 | 130 | 4,000 |
| SCR-1000 | 1,000 | 4,500 | 450 | 1,200 | 600 | 200 | 6,000 |
| SCR-1200 | 1,200 | 4,600 | 550 | 1,200 | 600 | 270 | 8,000 |
| SCR-1400 | 1,400 | 4,700 | 600 | 1,200 | 600 | 370 | 11,000 |
| SCR-1600 | 1,600 | 4,800 | 700 | 1,200 | 600 | 490 | 14,500 |
| SCR-1800 | 1,800 | 4,900 | 800 | 1,200 | 600 | 600 | 18,000 |
| SCR-2000 | 2,000 | 5,000 | 900 | 1,200 | 600 | 770 | 23,000 |
| SCR-2200 | 2,200 | 5,000 | 1,000 | 1,200 | 600 | 900 | 27,000 |
| SCR-2400 | 2,400 | 5,000 | 2000×450 | 1,200 | 600 | 1,100 | 33,000 |
| SCR-2600 | 2,600 | 5,100 | 2000×600 | 1,200 | 600 | 1,300 | 38,000 |
| SCR-2800 | 2,800 | 5,200 | 2000×600 | 1,200 | 600 | 1,500 | 44,000 |
| SCR-3000 | 3,000 | 5,300 | 2200×600 | 1,200 | 600 | 1,700 | 51,000 |
| SCR-3200 | 3,200 | 5,400 | 2300×700 | 1,200 | 600 | 1,900 | 58,000 |
| SCR-3400 | 3,400 | 5,500 | 2400×800 | 1,200 | 600 | 2,200 | 65,000 |
| SCR-3600 | 3,600 | 5,600 | 2600×800 | 1,200 | 600 | 2,400 | 73,000 |
| SCR-3800 | 3,800 | 5,700 | 3200×800 | 1,200 | 600 | 2,700 | 82,000 |
Standard fittings (acid-mist towers): spray system, packing media, moisture separator, inspection window / access manhole, overflow, drain & auto-refill ports, pressure gauge. Options: pH control, ORP control, chemical storage tank, chemical level control, circulation-tank level control. Non-standard sizes can be made to order. Source: Dingyu Waste Gas Treatment Engineering Brochure (February 2025 edition).
| Adsorbent | Form / size | Density (kg/m³) | Key performance |
|---|---|---|---|
| Pelleted activated carbon | Φ4×8 | 460–650 | Benzene adsorption 20–55%; carbon tetrachloride adsorption 30–70% (by iodine-value grade) |
| Honeycomb activated carbon | 100×100×100 mm, 1.5 mm cells | 250–380 | Benzene adsorption 30–70%; carbon tetrachloride adsorption 50–85% |
| SDG adsorbent, Type I | Φ3×5-10 | 650–750 | Adsorption capacity 25–35%; for NOx |
| SDG adsorbent, Type II | Φ3×5-10 | 730–830 | Adsorption capacity 40–50%; for acid gases such as H₂SO₄, HCl and HF |
Source: Dingyu Waste Gas Treatment Engineering Brochure (February 2025 edition), adsorption unit data table.